Voltage drop calculator
Check a circuit against the BS 7671 limits, find the maximum cable length for a load, or the smallest conductor that passes. Works for twin and earth, SWA, singles, flex and MICC in single-phase, three-phase and DC, plus thin-wall automotive cable for 12 V and 24 V systems. Results update as you type and the link in your address bar always reproduces them.
Voltage drop
— V
— % of — V
— V line-to-neutral equivalent
Limit — % = — V
- Voltage at load
- — V
- Design current Ib
- — A
- mV/A/m used
- —
- Max length at this load
- —
- Max current at this length
- — A
- Smallest size that passes
- —
- Power lost in cable
- — W
- Headroom
- — V
- Ct applied
- —
Notes
Working
Every size of this cable at the same load and length
Click a row to select that size.
| Size | mV/A/m | Drop | % | Max length | Max current | Result |
|---|
How the calculation works
The drop is the tabulated millivolts per amp per metre for the cable, multiplied by the design current and the one-way route length:
Vd (V) = mV/A/m × Ib × L ÷ 1000
The mV/A/m values come from Appendix 4 of BS 7671 (Tables 4D1B to 4G2B, cross-checked against manufacturer reproductions). Aluminium cables are not included; enter the Table 4H value manually. For 25mm² and above the tables give resistive (r), reactive (x) and impedance (z) figures. The calculator uses z unless you enter a power factor, in which case it uses r·cosφ + x·sinφ.
Three-phase values are line-to-line, so the percentage is taken against the 400 V line voltage. DC and extra-low-voltage cables that are not in the BS 7671 tables are worked from conductor resistance (BS EN 60228) at the chosen temperature, counting both legs of the run.
The limits
Table 4Ab of Appendix 4 gives the voltage drop that is deemed to satisfy Regulation 525.202, measured from the origin of the installation to the load:
| Supply | Lighting | Other uses |
|---|---|---|
| Public low-voltage supply | 3 % | 5 % |
| Private supply (generator, private transformer) | 6 % | 8 % |
For runs over 100 m the limit may be increased by 0.005 % per metre beyond 100 m, up to an extra 0.5 %. A final circuit fed from a sub-main shares the allowance with it, so enter the drop from the origin or check each leg against its share.
Ring final circuits, evenly distributed loads, parallel conductors and the conductor operating temperature factor Ct are all under Advanced options.